(item no. 4563561)
Built with the Fluke Connect® mobile app and desktop software compatibility, this logger provides you with the data you need to make critical power quality and energy decisions in actual time. Ideal for conducting energy studies and basic power quality logging, this logger automatically captures and logs over 500 power quality parameters which give you more visibility into the data you need to optimise system reliability and savings.
An optimised user interface, flexible current probes, and an intelligent measurement verification function that allows you to reduce measurement errors by digitally verifying and correcting common connection errors makes setup easier than ever and reduces measurement uncertainty. Access and share data remotely with your team via the Fluke Connect® app so you can maintain safer working distances and make critical decisions in real-time, reducing the need for protective equipment, site visits and check-ins. You can also quickly and easily chart and graph measurements to help identify issues and create detailed reports with the included Fluke Energy Analyse Plus software package.
If you’re looking for a power logger with the same great energy study capabilities and more advanced power quality logging capabilities, this energy logger is the ideal choice.
Features
- Versatile, three-phase Fluke Connect-compatible power logger for conducting basic energy and power quality studies
- Automatically captures and logs voltage, current, power, harmonics and associated power quality values
- Provides the highest safety rating in the industry: 600 V CAT IV/1000 V CAT III rated for use at the service entrance and downstream
- Automatically logs all measured values and stores more than 20 separate logging sessions
- Presents data locally on the logger or on the Fluke Connect mobile app and desktop software
- Allows you to power instrument directly from the measured circuit
- Allows reviewing measured values during logging sessions and before downloading for real-time analysis
- Event waveform snapshot
- High resolution RMS profile, along with date, timestamp and severity to capture dips, swells, and inrush currents and help pinpoint potential root causes of power quality issues
- Offers a bright, colour, touch-screen display for convenient field analysis and data checks
- Helps you capture the right data every time with a quick, guided, graphical user interface
- Reduces uncertainty about your connections with the intelligent verification function
- Allows you to complete field setups through the front panel or Fluke Connect App on your smartphone
- Comes with Energy Analyse Plus application software that enables you to analyse every detail of energy consumption and power quality health and create automated reports
Specifications Fluke 1736/B
Accuracy | |
Voltage | Range: 1000 V Resolution: 0.1 V Intrinsic Accuracy at Reference Conditions: ±(0.2% + 0.01%) |
i17xx-flex 1500 12″ | Range: 150 , 1500 A Resolution: 0.1, 1 A Intrinsic Accuracy at Reference Conditions: ±(1% + 0.02%), ±(1% + 0.02%) |
i17xx-flex 3000 24″ | Range: 300 , 3000 A Resolution: 1, 10 A Intrinsic Accuracy at Reference Conditions: ±(1% + 0.03%), ±(1% + 0.03%) |
i17xx-flex 6000 36″ | Range: 600 , 6000 A Resolution: 1, 10 A Intrinsic Accuracy at Reference Conditions: ±(1.5% + 0.03%), ±(1.5% + 0.03%) |
i40s-EL Clamp | Range: 4 , 40 A Resolution: 1, 10 mA Intrinsic Accuracy at Reference Conditions: ±(0.7% + 0.02%), ±(0.7% + 0.02%) |
Frequency | Range: 42.5 Hz to 69 Hz Resolution: 0.01 Hz Intrinsic Accuracy at Reference Conditions: ±(0.1%) |
Auxillary Input | Range: ±10 V dc Resolution: 0.1 mV Intrinsic Accuracy at Reference Conditions: ±(0.2% + 0.02%) |
Voltage Min/Max | Range: 1000 V Resolution: 0.1 V Intrinsic Accuracy at Reference Conditions: ±(1% + 0.1%) |
Current Min/Max | Range: Defined by accessory Resolution: Defined by accessory Intrinsic Accuracy at Reference Conditions: ±(5% + 0.2%) |
THD on Voltage | Range: 1000% Resolution: 0.1% Intrinsic Accuracy at Reference Conditions: ±0.5 |
THD on Current | Range: 1000% Resolution: 0.1% Intrinsic Accuracy at Reference Conditions: ±0.5 |
Voltage Harmonics 2nd to 50th | Range: 1000 V Resolution: 0.1 V Intrinsic Accuracy at Reference Conditions: ≤10 V: ±5% of reading, <10 V: ±0.5 V |
Current Harmonics 2nd to 50th | Range: Defined by accessory Resolution: Defined by accessory Intrinsic Accuracy at Reference Conditions: ≤3% of current range: ±5% of reading, <3% of current range: ±0.15% of range |
Unbalance | Range: 100% Resolution: 0.1% Intrinsic Accuracy at Reference Conditions: ±0.2 |