(item no. 2740465)
The ACDC-100 TRMS 1000A digital clamp meter offers superior accuracy, quality and reliability with all the basic measurement capabilities technicians need in an AC/DC current clamp meter. Use it to measure AC current to 800A, DC current to 1000A, and AC/DC voltage from 400.0 mV to 600V.
Its large jaws accommodate conductors up to 2″ (50 mm) in diameter and its enhanced ergonomic design make it a great choice for a clamp with professional digital multimeter capabilities.
Features
- True-rms
- Measures AC current to 800A and DC current to 1000A, AC/DC voltage to 600V, plus capacitance, and resistance
- Continuity beeper quickly identifies shorts and opens
- Relative zero mode displays the difference between the actual reading and a stored reference value and may be used with any function or range
- Data hold freezes the reading on the display for further analysis
- Diode test quickly finds voltage drops
- MAX capture function measures inrush current (30 mS response)
- Combines user friendly features such as a large, easy to read backlit digital display, auto power-off to conserve battery life, and a “third hand” test probe holder
- Rubber over-molded case absorbs shock and provides built-in probe storage
- Accommodates conductors up to 2.0″ (50mm) in diameter
- CAT III, 600V rated
- Includes deluxe carrying case, test leads, batteries (installed) and users manual
Specifications
FEATURE | ACDC-100 | ACDC-100 TRMS |
True-rms | – | • |
AC Current | 400.0 A, 800 A | |
DC Current | 400.0 A, 1000 A | |
Voltage AC/DC | 400.0 mV, 4.000 V, 40.00 V, 400.0 V, 600 V | |
Resistance | 400.0 O, 4.000 kO, 40.00 kO, 400.0 kO, 4.000 MO, 40.00 MO | |
Continuity | • | |
Capacitance | 500.0 nF, 5.000 µF, 50.00 µF, 500.0 µF, 3000 µF | |
Accommodates conductors | up to 2.0 (50 mm) in diameter |
Specifications | |
True-rms: | N/A |
DC Current: | 400.0 / 1000 A Accuracy: +/-(1.5% Rdg + 4 LSD) @ 0 to 800A ** |
AC Current: | 400.0 / 800 A Accuracy: +/-(1.5% Rdg + 5 LSD) @ 0 to 600A, 40 to 100Hz ** |
AC Voltage: | 400.0 mV 4.000 / 40.00 / 400.0 / 600V Accuracy: +/-(1.5% Rdg + 4 LSD) @ 4V to 400V ranges , 50 to 500 Hz** |
DC Voltage: | 400.0 mV 4.000 / 40.00 / 400.0 / 600V Accuracy: +/-(0.5% Rdg + 3 LSD) @ 4V to 400V ranges ** |
Resistance: | 400.0 Ohms 4.000 / 40.00 / 400.0 kOhms 4.000 / 40.00 MOhms Accuracy: +/-(0.6% Rdg + 4 LSD) @ 4 to 400 kOhms ranges ** |
Capacitance: | 500.0nF / 5.000 / 50.00 / 500.0 / 3000 uF Accuracy: +/-(3.5% Rdg + 6 LSD) |